Skip to content Skip to navigation menu
click to open Expanded view

A.P.C.S. A.P.C.S - Transducer Current AC - 2000Vrms isolation - ACT241-1410

  • A.P.C.S.
  • BW#: 01113453
  • Mfr#: ACT241-1410
  • UNSPSC#: 39101600
Login or Register to view price
QTY

Features
  • Double surge protection is standard with all Series 200 loop powered transmitters to prevent failure due to spikes induced by DC switched inductive loads

  • Input output relation can be direct or reverse acting

  • Input output isolation up to 2kV is achieved through the use of an internal current

  • transformer

  • Base calibration is set with 2 metal film resistors and removable coding plugs on the main board

  • These links provide a convenient and user-friendly means of changing the input range in the field from 0 - 1 Amp to 0 - 5 Amps

  • Any other 2 ranges are available upon request

  • Final calibration is trimmed using the front accessible zero and span 15-turn trim adjustments

  • A front mounted LED and a test socket verifies module function and assist in calibration checks without disconnection of output wires


Applications
  • Used in load monitoring

  • The ACT241 is used in 12V battery systems


Specifications

  • Size: 23.5W x 71.5H x 109D (mm)

  • Mounting: Clip for 35mm DIN-Rail

  • Housing material: ABS

  • Connection: Screw terminals

  • Weight: 0.106 kg

  • AS-1384-1973: Class 0.2

  • Response time: < 500mS

  • Input range: 0.5A up to 10A

  • 1A or 5A standard, (50, 60 or 400Hz Sine)

  • Protection class: IP40 (IP65 use additional enclosure)

  • Calibration Accuracy: <0.2% from 10% up to 100% of range

  • Linearity: <0.2% from 10% up to 100% of range

  • Frequency dependence: <0.01%/Hz from 40 to 400Hz

  • Ambient operating range: -20...+70°C

  • Temperature drift error: <0.5% within operating range

  • Supply voltage: 7.5 - 40V continuous (50V 30 seconds)

  • Load change effect: < 0.1% up to RL max

  • Front zero adjust: + 20% / -10% typical

  • Front span adjust: ± 25% typical

  • Overload continuous: 150% of rated input

  • Short term (2 sec): 20 times rated input

  • Input/output isolation: 2kV rms continuous

  • Electromagnetic compatibility: Complies with AS/NZS 4251.1 (EN 50081.1)

  • The ACT241 accepts AC current from current transformer or direct load current ranging from 0.5A up to 10A

  • Standard output is 4 - 20mA with a minimum supply voltage of 7.5V

  • Other factory set output configurations are 10 - 50mA loop powered and 0 - 10mA, 0 -20mA or voltage output in 3-wire connection

Minimum sell quantity:

Order Quantity Multiple:

Technical Specifications

Alternate Products