Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric TeSys GB2 GB2CD05 Thermal Magnetic Circuit Breaker - 1P+N - 0.5A Icu - 50kA - 240V

  • Schneider Electric
  • BW#: 00469493
  • Mfr#: GB2CD05
  • UNSPSC#: 39121601
Login or Register to view price
QTY

Features
  • Compliance with standards: IEC 947-1, 947-2; Certifications: IEC, CSA and UL
  • 12 ratings available from 0.5 to 20 A: 1-pole (GB2 CB), 1-pole + neutral (GB2 CD), 2-pole (GB2 DB), Magnetic tripping threshold set between 12 to 16 In (withstands current peaks generated by many industrial components.)
  • 2 ratings available: 0.5 and 1 A: 1-pole version, Magnetic tripping threshold set between 5 and 7 In
  • 15 mm wide for 1-pole
  • 30 mm wide for 2-pole
  • Clear indication of "I" and "O" positions on the operators


  • Applications
  • TySys GB2 is a flexible range of thermal-magnetic circuit breakers that enable reliable protection of industrial equipment control circuits, such as power supplies, electronic systems protection, PLC, control circuits and all small devices capable of generating a high current peak


  • Specifications

    • Utilisation category: DC-13 conforming to IEC 60947-5-1

    • Magnetic Tripping Current: 6.6 A

    • Poles description: 1P + N

    • Product or component type: Circuit breaker

    • [Ics] Rated Service Short-Circuit Breaking capacity: 100 % at 110 V AC 50/60 Hz conforming to IEC 60947-2

    • Network Frequency: 50/60 Hz conforming to IEC 60947-2

    • Trip unit technology: Thermal-magnetic

    • Breaking capacity: Icu = 50 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

    • Breaking capacity: Icu = 1 kA at 48 V DC conforming to IEC 60947-2

    • Breaking capacity: Icu = 1.5 kA at 24 V DC conforming to IEC 60947-2

    • Product name: TeSys GB2

    • [Ics] Rated Service Short-Circuit Breaking capacity: 25 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2

    • Breaking capacity: Icu = 50 kA at 110 V AC 50/60 Hz conforming to IEC 60947-2

    • Range: TeSys

    • Utilisation category: Category A conforming to IEC 60947-2

    • Utilisation category: DC-12 conforming to IEC 60947-5-1

    • Network type: AC/DC

    • Device short name: GB2

    • Device application: Control

    Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Number of Pole 1P + N
    Type Circuit Breaker
    Current Rating 0.5 A
    Terminal Connection Connector 1 Cable(S) 0.75-6 Mm²Solid Without Cable End
    Connector 2 Cable(S) 0.75-4 Mm²Solid Without Cable End
    Connector 1 Cable(S) 0.75-4 Mm²Flexible With Cable End
    Connector 2 Cable(S) 0.75-2.5 Mm²Flexible With Cable End
    Width 15 mm
    Height 74 mm
    Length 74 mm
    Colour White
    Weight 70 g
    Rated Impulse Withstand Volt 4 Kv Conforming To Iec 60947-2
    Trip Unit Technology Thermal-Magnetic
    Mounting Mode plate
    rail
    Network Frequency 50/60 Hz conforming to IEC 60947-2
    Air Temperature for Storage -40-80 °C
    Air Temperature for Operation -20-60 °C
    Rated Operational Voltage 250 V AC 50/60 Hz conforming to IEC 60947-2
    277 V AC 60 Hz conforming to CSA C22.2 No 235
    277 V AC 60 Hz conforming to UL 1077
    48 V DC
    Alternate Products