Skip to content Skip to navigation menu
click to open Expanded view

Terasaki - Tb2 MCCB 50Ka 4P 400A Electronic - S400NE4400

  • TERASAKI
  • BW#: 00814644
  • Mfr#: S400NE4400
  • UNSPSC#: 39121616
Login or Register to view price
QTY

Specifications
  • Service Information: Product is not repairable
  • Product Series: TemBreak 2 MCCB
  • Standards Compliance: IEC 60947-1, IEC 60947-2, AS 60947-2, AS/NZS 3947.1, AS/NZS 3947.2, EN 60947-2, JIS C 8201-2-1 Ann.1
  • Certifications: CE, ASTA
  • Shipping Approvals: Contact NHP
  • Component Type MCCB: MCCB AC
  • Standard Installation Method: Front Connection
  • Trip Unit Protection Type: Electronic
  • In, Rated Current at 45°C: 400 A @45°C
  • Ics, Rated Service Short-Circuit Breaking Capacity, AC (IEC 60947): 100 % Icu
  • Ir, Thermal Trip Current, Max: 400 A
  • Ir, Thermal Trip Current, Min: 160 A
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 220/240V AC: 85 kA @220/240VAC
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 400/415V AC: 50 kA @400/415VAC
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 440V AC: 45 kA @440VAC
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 525V AC: 30 kA @525VAC
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 690V AC: 20 kA @690VAC
  • Depth: 103 mm
  • Frame Size: 400 AF size
  • Height: 260 mm
  • Number of Poles: 4
  • Electrical Service Life at Un, In: 4500 cycles
  • Mechanical Service Life: 15000 cycles
  • Thermal Trip Type: Adjustable type
  • Ui, Rated Insulation Voltage: 800 V (rms)
  • Un, Nominal Operational Voltage, AC: 690 V AC
  • Weight: 5.7 kg
  • Width: 185 mm
  • Reverse Connection Of Supply Possible: Yes
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type MCCB AC
    Number of Pole 4
    Colour White
    Height 260 mm
    Width 185 mm
    Weight 5.7 kg
    Rated Current 400 A @45°C
    Rated Insulation Voltage 800 V (rms)
    Trip Unit Technology Electronic