Skip to content Skip to navigation menu
click to open Expanded view

Wago - Compact 2-Pole Splicing Connector Ex - 0.5 .. 6.0 mm² 37A with Operating Levers - Transparent - *221-511 Carrier Required - Pack 50 - 221-682

  • Wago
  • BW#: 01380217
  • Mfr#: 221-682
  • UNSPSC#: 39121432
Login or Register to view price
QTY

Features
  • Ease of use – pull the lever up, insert a conductor and push the lever back down

  • Available as 2-, 3- and 5-wire connectors

  • Easily terminate conductors from 0.5 to 6 mm²

  • Connection of all conductor types

  • Time savings for installers and device manufacturers

  • Quickly install devices with higher levels of power consumption

  • Safely install long cable runs with larger conductor cross sections

  • Mounting carrier for installation conforms to standards

  • Working voltages of 275 V or 440 V

  • ATEX (Ex 2 II G), IECEx (Ex eb IIC Gb) Zone 1, 2

  • IECEX (Ex eb IIC Gb), American Ex (AEx eb IICGb) / Class 1, Zone 1

  • Width 16 mm / 0.63 inch

  • Height 10.1 mm / 0.398 inch

  • Depth 21.1 mm / 0.831 inch

  • Weight 3 g

  • Color transparent

  • Flammability class per UL94 V2

  • Color of actuator light gray


Specifications

  • Electrical data

  • Ratings per IEC/EN 60664-1

  • Ratings per EN 60664

  • Approvals per UL 1059

  • Rated voltage UL (Use Group C) 440 V

  • Rated current UL (Use Group C) 30 A

  • Approvals Ex

  • Ratings per ATEX: PTB 19 ATEX 1001 U / IECEx: PTB 19.001 1U (Ex eb IIC Gb)

  • Rated voltage EN (Ex e II) 440 V

  • Rated current (Ex e II) 37 A

  • Connection data

  • Connection technology CAGE CLAMP®

  • Actuation type Lever

  • Connectable conductor materials Copper

  • Nominal cross-section 6 mm²

  • Solid conductor 0.5 … 6 mm² / 20 … 10 AWG

  • Stranded conductor 0.5 … 6 mm² / 20 … 10 AWG

  • Fine-stranded conductor 0.5 … 6 mm² / 20 … 10 AWG

  • Strip length 12 … 14 mm / 0.47 … 0.55 inch

  • Total number of connection points 2

  • Total number of potentials 1

  • Wiring type Side-entry wiring

  • Safety information 1:

  • The permissible operating voltage of the connector with carrier (440 V or 275 V) depends on the mounting type

  • Safety information 2:

  • Only approved in conjunction with a mounting carrier (221-511). Other carriers are possible, see certificate/file

  • The connectors must be installed in an enclosure meeting the requirements of a recognized protection type per EN 60079-0, Section 1 or EN 60079-31

  • When installing the connectors in an enclosure of protection type “eb” (increased safety) per EN 60079-7, the clearances and creepage distances of Table 2 for this standard must be observed

  • See point 1 for the use of accessories

  • The connectors can be used both in Group II and Group I, as the standard requirements are identical in this case

  • The use of these components requires a new assessment by a notified certification agency

Minimum sell quantity:

Order Quantity Multiple:

Technical Specifications

Alternate Products